Chilled Water Clamp LKS 13
                      
                      
                  Application
Suitable for secure prevention of condensation water at the pipe support location of refrigeration and cold-water pipelines. An optimal diffusion-tight connection with the pipe insulation is easily and safely achieved by fixing usual insulation materials to the clamp faces using adhesive. Recommended up to -0°C at normal ambient condition.
Scope of delivery
Consisting of pipe clamp and insulation insert. The one-piece insulation insert comprising two joined PUR elements forms a comprehensive connection between PUR element and pipe clamp all around the  pipe. 
The outer edges of the PUR elements are equipped with elastomer foam and coated by a black aluminium foil.
|  Type |  Nominal thickness of  the insulation [mm]  |  Size |  Length of PUR element b [mm]  | 
|---|---|---|---|
|  LKS 13  |  13 |  10 - 89 102 - 168  |  50 100  | 
Technical Data
|  Size [mm]  |  Working load  (tension)  |  Tightening torque [Nm]  | 
|---|---|---|
| 13-10 - 13-12 | 0.3 kN |  2 | 
| 13-15 - 13-16 | 0.4 kN |  2 | 
| 13-18 - 13-26 | 0.5 kN |  2 | 
| 13-28 - 13-48 | 0.6 kN |  2 | 
| 13-50 - 13-57 | 1.0 kN |  2 | 
| 13-60 - 13-64 | 1.1 kN |  2 | 
| 13-70 | 1.2 kN |  2 | 
| 13-76 - 13-80 | 1.3 kN |  2 | 
| 13-89 | 1.4 kN |  2 | 
| 13-102 | 1.6 kN |  2 | 
| 13-108 - 13-114 | 1.7 kN |  2 | 
| 13-125 | 1.9 kN |  2 | 
| 13-133 | 2.0 kN |  2 | 
| 13-139 | 3.3 kN |  2 | 
| 13-160 | 3.7 kN |  2 | 
| 13-168 | 3.8 kN | 2 | 
The unsupported lengths as listed in DIN 1988 may be applied for types LKS 13 and LKS M 19 to 168.
The regulations of DIN 4140 have to be respected (an existing gap has to be sealed with sealant). Sealant DP 30/45 see Chapter "Fixed Point Packages".
|  Clamp material: |  Steel, electro-galvanised | 
|  Insulation insert:  |  Free of halogens | 
|  PUR core: |  Specific gravity 80 or 120 kg/m3  | 
|  Thermal conductivity: |  λ = 0.024 - 0.026 W/(mK) at 0°C λ = 0.038 W/(mK) at 10°C λ = 0.040 W/(mK) at 40°C  | 
|  Fire resistance: |  EL (DIN EN 13501-1) | 
|  Temperature range: |  -40°C up to +105°C | 
|  Insulation insert: |  Up to 18 dB(A) | 
|  Storage temperature: |  ≥ 10°C | 
* = Delivery time: 10 workdays