Chilled Water Clamp LKS 19
                      
                      
                  Application
Suitable for secure prevention of condensation water at the pipe support location of refrigeration and cold-water pipelines. An optimal diffusion-tight connection with the pipe insulation is easily and safely achieved by fixing usual insulation materials to the clamp faces using adhesive. Recommended up to -0°C at normal ambient condition.
Scope of delivery
Consisting of pipe clamp and insulation insert. The one-piece insulation insert comprising two joined PUR elements forms a comprehensive connection between PUR element and pipe clamp all around the  pipe. 
The outer edges of the PUR elements are equipped with elastomer foam and coated by a black aluminium foil.
|  Type |  Nominal thickness of  the insulation [mm]  |  Size |  Length of PUR element b [mm]  | 
|---|---|---|---|
|  LKS 19 |  19 |  15 - 89 102 - 273  |   50 100  | 
Technical Data
|  Size [mm]  |  Working load (tension)  |  Tightening torque [Nm]  | 
|---|---|---|
| 19-15 - 19-16 | 0.4 kN |  2 | 
| 19-18 - 19-20 | 0.5 kN |  2 | 
| 19-22 - 19-48 | 0.6 kN |  2 | 
| 19-50 | 1.1 kN |  2 | 
| 19-54 - 19-60 | 1.2 kN |  2 | 
| 19-64 - 19-70 | 1.3 kN |  2 | 
| 19-76 | 1.4 kN |  2 | 
| 19-80 | 1.5 kN |  2 | 
| 19-89 | 1.6 kN |  2 | 
| 19-102 | 1.7 kN |  2 | 
| 19-108 - 19-110 | 1.8 kN |  2 | 
| 19-114 | 1.9 kN |  2 | 
| 19-125 | 2.0 kN |  2 | 
| 19-133 | 2.1 kN |  2 | 
| 19-139 | 3.5 kN |  2 | 
| 19-160 | 3.9 kN |  2 | 
| 19-168 | 4.1 kN |  2 | 
| 19-180 | 4.3 kN |  2 | 
| 19-200 | 4.7 kN |  2 | 
| 19-219 | 5.1 kN |  2 | 
| 19-225 | 5.2 kN |  2 | 
| 19-250 | 5.7 kN |  2 | 
| 19-273 | 6.1 kN | 2 | 
The unsupported lengths as listed in DIN 1988 may be applied for types LKS 13 and LKS M 19 to 168.
The regulations of DIN 4140 have to be respected (an existing gap has to be sealed with sealant). Sealant DP 30/45 see Chapter "Fixed Point Packages".
|  Clamp material: |  Steel, electro-galvanised | 
|  Insulation insert:  |  Free of halogens | 
|  PUR core: |  Specific gravity 80 or 120 kg/m3  | 
|  Thermal conductivity: |  λ = 0.024 - 0.026 W/(mK) at 0°C λ = 0.038 W/(mK) at 10°C λ = 0.040 W/(mK) at 40°C  | 
|  Fire resistance: |  EL (DIN EN 13501-1) | 
|  Temperature range: |  -40°C up to +105°C | 
|  Insulation insert: |  Up to 18 dB(A) | 
|  Storage temperature: |  ≥ 10°C | 
* = Delivery time: 10 workdays